The LD Series are based on microprocessor technology providing reliable and accurate measurement of oxidation reduction potential (ORP).
The LD Digital Series is the ideal partner to manage chemical treatment programs.
| Range | -1000 to 1000 mV |
|---|---|
| Resolution | ± 1 mV |
| Display | LCD Backlit graphic display |
| Controls | Digital keyboard |
| Calibration | Manual |
| Set Points | Two On/Off; Two Digital Proportional |
| On/Off Output | 2 Voltage Output |
| Serial Port | RS232 |
| Input Impedance | Greater Than 1012 Ω |
| Delay | Programmable "Power-on" delay |
| Max Resistive Load | 5A - 220 VAC |
| Power Supply | 90 - 240 VAC; 50-60Hz |
| Power Consumption | 10W |
| Fuse | Output, instrument and alarm fuse protections |
| Galvanic Isolation | Yes, 0-20 mA Output |
| Casing Material | ABS - IP65 |
| Mounting | Wall |
| Temperature Unit | °C |
| Temperature Compensation | 0 - 100 |
| Dimensions | 225 x 215 x 125 mm |
| Net Weight | 1.2 Kg (2.6455 lbs) |